A battery planner saved 2.63 times more than a simple price rule
A data-center battery paired with rolling forecasts and dynamic programming saved far more than a fixed-threshold strategy in simulations—but the forecast
€5,029/day: average simulated savings from forecast-guided dispatch at one battery size.
The same battery, serving the same data center, saved €5,029 a day under one dispatch strategy and €1,959 under another. The difference was not new hardware. It was a better attempt to predict when electricity would be expensive—and how much power the data center would need at that moment. In simulations, a forecasting-and-planning framework delivered 2.63 times the savings of a simple rule that charged below one price threshold and discharged above another (Van Ham et al., 2026).
That matters because data centers are becoming enormous and increasingly flexible electricity customers. Their servers cannot simply stop whenever the grid is strained, but a battery can shift some purchases across time: charge when electricity is cheap, then discharge when prices rise. The hard part is choosing the right moment. A price spike is not automatically an opportunity if the battery is empty, the data center’s load is high, or the value of stored energy later is greater.
The paper’s central idea is to forecast electricity prices and data-center loads together, then use those forecasts to plan battery operation. “Together” here means that both evolving signals enter the dispatch decision; the paper describes separate stochastic models for prices and loads, rather than demonstrating a single jointly estimated price-load process. The distinction matters, but the practical insight is clear: storage decisions should account for both the market and the facility using the power.
Forecast-guided dispatch raises simulated daily savings
Mean daily savings for the 100-MW data center and 12-MW/36-MWh battery benchmark.
| Label | Value |
|---|---|
| Mean daily cost savings | 5,029 €/day |
The Science
A battery is a time-shifting device, not a power source. It buys electricity earlier, stores some of it, and later reduces the amount the data center must purchase from the grid. Every cycle has limits: the battery cannot charge or discharge faster than its rated power, it cannot hold more than its energy capacity, and energy is lost in charging and discharging. The researchers also assign a cost to battery wear, so a small price difference may not justify an extra cycle.
The research team—Matthew Van Ham, Yiping Liu and Xiaozhe Wang—builds its forecasting system around polynomial diffusion models, or PDMs. In plain terms, a PDM describes how an underlying set of fluctuating signals changes over time, then maps those signals into observed prices or loads. The latent signals are mean-reverting: after a disturbance, they tend to drift back toward a typical level. Polynomial mappings make the observed series more flexible than a simple bell-shaped distribution, allowing skewed movements and occasional large price changes.
Both price and load contain regular patterns as well as surprises. Electricity demand and market prices can vary by hour and day of the week, so the authors first represent daily and weekly rhythms with Fourier terms—smooth repeating waves—and subtract those seasonal patterns. The remaining deviations are modeled with latent factors that can move at different speeds. For data-center load, the authors point to Google power traces in which deseasonalized residuals look approximately Gaussian, suggesting that a comparatively modest nonlinear model may be adequate.
The unusual computational feature is that PDM forecasts can be calculated without repeatedly simulating thousands of possible futures. The authors’ model has a mathematical structure in which expected future values of polynomial functions can be computed with finite-dimensional matrix operations. That gives a conditional forecast: given the latest estimated state, what is the expected price or load over a future delivery interval?
To track that hidden state, the framework uses an unscented Kalman filter (UKF). The filter combines the model’s expected evolution with each new observation, updating its estimate every 15 minutes. A Kalman filter is a method for inferring an unobserved system state from noisy measurements; the “unscented” version is designed to handle nonlinear relationships more effectively than a basic linear filter. Model parameters are calibrated offline, while the state and forecasts are refreshed as observations arrive.
Those forecasts feed a dynamic program (DP), a method that compares present choices by accounting for their consequences later. At each 15-minute update, the system considers feasible charging and discharging actions and estimates the resulting electricity bill, battery wear, and value of the energy left in storage. It implements only the first action, then forecasts again at the next update. This rolling-horizon approach lets the schedule adapt as the market and facility conditions change.
The evaluation uses two different sources of historical data: German intraday electricity prices and publicly available Google data-center power traces. The authors calibrate price and load models and test them out of sample. They then generate 1,000 simulated trajectories to examine savings, rather than report a live trial at a data center. That design can test the logic systematically, but it is not the same as proving performance in an operating facility.
What They Found
The PDMs broadly matched the observed average price and load over a five-day out-of-sample period. Simulated mean electricity prices were €116.2 per megawatt-hour, compared with €117.6/MWh realized. For normalized load, the simulated mean was 0.7171, against 0.7143 in the observed data. Those close averages are encouraging, but averages are only one part of a forecast.
The model also produced too much variation, especially in electricity prices. Its simulated price standard deviation was €67.9/MWh, while the realized standard deviation was €53.5/MWh. Load variability was also somewhat high: 0.0527 simulated versus 0.0489 realized. In battery dispatch, this matters because the apparent value of waiting for a spike depends on how likely and how large the model thinks that spike will be.
Price forecasts get the average close, but spread too wide
PDM-simulated and realized mean and standard deviation over a five-day out-of-sample period.
| Label | Value |
|---|---|
| Mean | 116.2 €/MWh |
| Standard deviation | 67.9 €/MWh |
Load forecasts were close in mean and variability
PDM-simulated and realized normalized data-center load over a five-day out-of-sample period.
| Label | Value |
|---|---|
| Mean | 0.7171 normalized load |
| Standard deviation | 0.0527 normalized load |
In the headline benchmark, the researchers modeled a 100-megawatt data center with a 12-MW/36-MWh battery. The dynamic-programming strategy saved an average of €5,029 per day across simulations. A rule-based comparator—charge below €80/MWh, discharge above €150/MWh, and otherwise stay idle—saved €1,959 per day. That is a 2.57-fold improvement in this particular benchmark, not the paper’s 2.63 aggregate figure.
The 2.63 ratio comes from a separate comparison across four battery configurations serving a 20-MW data center. The paper reports that dynamic programming delivered between 2.53 and 2.74 times the savings of the rule-based strategy across those configurations, with an aggregate ratio of 2.63. The excerpted paper content does not provide the individual Table I savings, so those configuration-level euro values cannot be reproduced here.
The analysis of storage duration points in the same direction. Longer-duration batteries increased daily savings under both strategies, but the gains diminished as capacity grew. The DP-to-rule-based savings ratio generally rose with duration and then leveled off, suggesting that forecasts can help a planner use longer storage more effectively than fixed thresholds do. This does not mean longer batteries always pay for themselves: the study reports simulated operating savings, not a full investment appraisal that includes battery purchase and installation costs.
Why This Changes Things
The result challenges a familiar, appealing shortcut: if prices are low, charge; if they are high, discharge. A fixed threshold ignores what the battery has already done, what it can do next, and what load the data center is expected to carry. A planner can sometimes preserve energy for a more valuable future interval or avoid cycling when the expected price spread is too small to compensate for losses and wear.
The load forecast is not a side detail. A data center’s electricity bill depends on market prices multiplied by the amount of electricity it draws. If demand changes, a schedule that looked profitable using a price forecast alone may turn out differently. Forecasting both signals gives the dispatch optimizer a more operationally relevant picture of the purchase it is trying to manage.
There is also a useful engineering argument here: sophisticated forecasting does not have to mean an unworkable amount of computation. The PDM’s closed-form conditional expectations let the researchers update forecasts through matrix operations, while the UKF tracks the changing state. That tractability is important in a setting where a decision is refreshed every 15 minutes and has to fit into an existing control system.
More broadly, batteries at large electricity consumers could become one part of a more flexible grid. They cannot eliminate the electricity appetite of cloud computing or AI, and this paper does not measure emissions or prove that the proposed approach improves grid reliability. But shifting purchases away from expensive intervals can help an operator manage costs, while making a large, steady load somewhat more responsive to market conditions. Whether that flexibility benefits the wider system depends on when batteries charge, how the market settles deviations, and what other grid constraints are binding.
What's Next
The biggest caveat is that the model is better at matching averages than at matching the full spread of price outcomes. Because price volatility was overstated in the test period, dispatch could react to risks that were larger in the model than in reality. The mismatch does not erase the observed simulated advantage over the threshold strategy, but it makes calibration and testing across more market conditions essential.
A second caveat is the gap between a simulation and a control room. The study pairs German prices with Google data-center load traces and evaluates simulated trajectories; it does not demonstrate that an operator deployed the system and earned those savings. A field test would need to account for real bidding and settlement rules, telemetry delays, battery outages, operational safety margins, and the possibility that other market participants respond to the same price signals.
The paper also models prices and loads separately. Its dispatch objective uses both forecasts, but the paper does not establish how correlated price and load shocks behave in the real operating environment. If high prices tend to coincide with particular load conditions, that relationship could matter to both forecast quality and the value of storage. A richer joint model would be one way to test that question, rather than assuming the two forecast errors are unrelated.
Finally, the authors identify risk-aware operation as a next step. Their current dispatch is based on conditional forecasts, while future work would incorporate higher-order predictive moments—the spread and shape of possible outcomes, not just their expected values. That could help an operator decide how much value to place on a likely saving versus protection against an unusually costly interval.
For data centers, the promise is practical rather than magical: better timing could make existing batteries more useful without asking servers to become dramatically more flexible. The next test is whether this forecasting advantage survives real market operations, imperfect forecasts, and the full economics of battery ownership. If it does, a data center’s battery can become more than backup equipment—it can be a carefully timed tool for managing one of the digital economy’s largest physical costs.