A fouling curve can’t tell you what’s clogging the heat exchanger
A familiar rising curve may look like a fingerprint of deposition or removal. This paper shows it often isn’t—and explains what measurements can reveal instead.
The mean fouling curve can be identical for radically different deposition and removal mechanisms.
A heat exchanger can trace a smooth, familiar rise in fouling resistance while the material coating it arrives in bursts, accumulates gradually, or is repeatedly stripped away. The curve operators often treat as evidence of a particular mechanism may not identify that mechanism at all. Simone Casolo’s analysis shows that, under broad assumptions, very different microscopic stories produce exactly the same average curve. The shape tells us how quickly fouling accumulates on average—and, in some cases, how quickly it relaxes. It does not tell us how deposits are made.
That distinction matters because a heat exchanger is not a passive ledger. Deposits reduce heat transfer, consume fuel and operating margin, and eventually make cleaning necessary. If a familiar curve is mistaken for proof of one physical process, operators may build maintenance decisions or mechanistic explanations on evidence the curve cannot provide. The paper’s central finding is a useful restraint: a good fit is not necessarily a good diagnosis.
The Science
Fouling is commonly tracked as a resistance to heat transfer. In practice, that resistance is reconstructed from temperature and flow measurements rather than read directly from a sensor. A small change in resistance between observations can therefore be smaller than the error in the inferred value—a crucial limitation when trying to spot the irregularities that might reveal what deposits are doing.
Two classic models give operators recognizable shapes. The Kern–Seaton model assumes that material deposits at a steady rate while removal grows in proportion to the amount already present. The result rises toward a plateau: as the deposit grows, removal catches up. The Ebert–Panchal family describes a net growth rate determined by deposition and a shear-related opposing term; in its net-fouling regime, resistance grows approximately linearly. Both are useful descriptions of records. The question is whether either curve uniquely identifies the process that made it.
Casolo reframes deposition as a sequence of non-negative random increments. They may represent particles, clusters, flakes or other effective events; their individual physical identity need not be known. The increments are assumed statistically stationary (their probabilities do not drift over time), independent over non-overlapping periods, and never negative. Under these conditions, cumulative deposition is a mathematical object called a subordinator: a process that only increases, though it may jump abruptly or accumulate through many tiny changes.
The model also assumes steady operating conditions, additive resistance contributions, and a deterministic removal rule. It leaves out feedback in which growing deposits change flow or temperature, and it does not cover every state-triggered detachment process. Those boundaries are important. The result is not that mechanisms never matter; it is that the average curve alone cannot distinguish them within this broad, clearly specified setting.
The key mathematical move is simple: take the average of the accumulation-and-removal balance. With no removal, the average of the deposit increases at the mean deposition rate. With removal proportional to the current deposit, the average follows the same asymptotic equation as Kern–Seaton. Expectation smooths away the details of event size and timing. Whether material arrives as frequent small increments or rare large ones, the mean is the same if the mean rate is the same.
What They Found
The first result is a direct challenge to a common reading of fouling records. A linear mean does not establish that removal is absent. An asymptotic mean does not establish a unique removal mechanism. Under first-order removal, the mean approaches a plateau set by the ratio of the average deposition rate to the removal rate. The microscopic deposition law can vary without changing that result (Casolo, 2026).
That point also clarifies how to read the Ebert–Panchal opposition between deposition and shear. The opposing term can be interpreted as suppression—fewer arriving particles stick—or as actual erosion, which removes material between deposition events. In the model, those interpretations share a mean trajectory but do not have the same fluctuations. The average alone cannot decide between them.
Where, then, does the missing information go? First into the variance: how far individual increments or repeated runs scatter around the mean. Under first-order removal, the paper derives a variance that approaches a plateau of , where is the deposition variance rate and is the removal rate constant. By contrast, under pure deposition the variance grows with time. This difference gives some removal processes a signature that survives after the mean has settled.
A particularly notable case is intermittent sloughing: random events that remove a fraction of the deposit. The paper finds that this can leave persistent scatter even when deposition itself becomes smooth. The mean may look much like another asymptotic curve, but the variability remains. In principle, a long record that has reached a plateau could therefore help distinguish removal behavior through its scatter—not its average.
The deposition law itself is harder to identify. Casolo examines a family of event-size distributions with a shape parameter that changes how deposition is apportioned among small and large events. The family is constructed so that its members share the same mean and variance rates. Their differences emerge only in higher-order statistics, such as skewness (asymmetry) and kurtosis (the weight of unusually extreme increments).
Those higher-order signatures are fragile. Thermal resistance is inferred from noisy measurements, and the noise attenuates the very statistical features that separate event distributions. The paper’s analysis says that the record needed to distinguish deposition laws grows as the fourth power of conductance error. That steep scaling is a warning: improving measurement accuracy can matter far more than merely collecting a modestly longer record, and at realistic accuracy the needed record may be out of reach.
The paper also connects event variability to an effective number of deposition events. When a sampling window contains many size-weighted events, their combined deposit becomes relatively smooth; when only a few events carry most of the material, growth looks lumpy or intermittent. This provides a way to think about why a process with countless tiny events can still behave irregularly: a few large events may dominate the deposited mass.
For operators, the practical target is often not identifying every deposition event but predicting when resistance will cross a cleaning limit. The study finds that the specific deposition law matters chiefly when the threshold is close. Farther from the limit, the average rate and uncertainty around that rate dominate the forecast. That is a pragmatic result: the data may support useful maintenance predictions even when they cannot support a confident microscopic diagnosis.
Why This Changes Things
The result separates two questions that are often blurred together: “What is the average fouling trajectory?” and “What physical process is producing it?” A curve fit can answer the first. It may estimate a net deposition rate and a relaxation time. But a single mean trajectory generally cannot answer the second. Several distinct mechanisms—erosion, particle detachment, intermittent sloughing, or changes in effective deposition—can produce the same broad shape.
This is not an argument against mechanistic models. It is an argument for asking them to earn their interpretations with evidence beyond the curve. A model may explain how a rate changes with wall shear, temperature, concentration or operating conditions. But one record at one operating point, especially when reduced to its mean trend, cannot reliably identify those dependencies. Comparing conditions, measuring variability, and incorporating independent physical observations may be necessary.
The distinction matters beyond heat exchangers. Many systems are monitored through aggregate signals: a mean level, a smooth trend, a total count. Such summaries can be excellent for tracking performance while concealing the processes underneath. Casolo’s framework makes the information loss explicit. Averaging is not merely a convenient visualization; it discards the event-level details that might distinguish mechanisms.
There is also a positive operational implication. If cleaning decisions depend mostly on mean rate and its uncertainty except near the limit, operators may not need to solve the entire microscopic puzzle to improve maintenance. Better estimates of the net rate, more reliable uncertainty bounds, and careful calibration of the thermal reconstruction may deliver more value than selecting a theoretically elaborate deposition law from a noisy resistance trace.
The paper is not claiming all curves are interchangeable in every real plant. Its assumptions exclude important feedbacks: as deposits constrict a flow passage, for example, they can change shear and temperature, and those changes may alter subsequent deposition or removal. Ageing or consolidation can also change thermal resistance without a proportional change in deposited mass. Once such effects matter, the simple universal mean laws need not hold. The framework is strongest as a statement about what can be inferred under stationary additive conditions—and as a reminder to test whether those conditions are plausible.
What’s Next
The next step is not simply to fit the same resistance record with more candidate curves. It is to design monitoring that can distinguish the questions the mean cannot. Replicate runs, higher-frequency observations, or independent measurements of deposit mass and surface condition could help determine whether scatter comes from deposition bursts, removal events, or measurement error. The most useful monitoring plan may be one that deliberately captures variability rather than smoothing it away.
Noise reduction is especially important if the aim is to identify the distribution of deposition events. Since that information resides in higher cumulants, it is precisely the information most vulnerable to errors in reconstructed conductance. The fourth-power relationship reported by the paper makes clear why “just collect more data” may not be enough. Better instruments and better experimental design could be prerequisites, not optional refinements.
There are also clear boundaries for future theory. Real heat exchangers operate through changing flows, temperatures and fouling states; deposits can age, crack, detach in state-dependent ways, and alter the conditions that created them. Extending the analysis to those coupled situations will require models in which the deposition rate or removal law depends on the evolving surface and operating state. Then the mean itself may carry more mechanistic information—but only if the feedbacks are measured and represented well.
For now, the most defensible reading of a familiar fouling curve is modest and useful. It summarizes an average balance, not a microscopic confession. That distinction can keep operators from overinterpreting a smooth line, while directing attention toward the measurements that matter for action: rate, uncertainty, and how close the system is to its cleaning limit.