78,484 largest case buses

A public grid model with 78,484 buses is not a map of the real Eastern U.S. power system. It is something more useful for research: a large, electrically solvable, openly shareable test bed that does not disclose protected infrastructure data. EPIGRIDS offers seven such cases, from a 250-bus New England model to an Eastern Interconnection-scale network, all built by a method distinct from the one behind many of the synthetic grids researchers already use (Snodgrass et al., 2026).

That distinction matters because the algorithms tested on these networks are increasingly consequential. Engineers use them to study power flows and outages; researchers also train artificial-intelligence systems to approximate costly grid calculations. If nearly every model is trained and evaluated on networks created in much the same way, a system may learn the construction method’s signature as much as the physics. EPIGRIDS adds another family to the test set—while also documenting where its models depart from real networks and what users must handle with care.

(d) Eastern, 78,484 buses
(d) Eastern, 78,484 buses Source: Jonathan M. Snodgrass, Scott Greene

The Science

A transmission grid is a physical network of substations, lines, transformers, and generators. Its detailed real-world operating models are treated in the United States as critical energy infrastructure information, or CEII, and are not available for unrestricted public use. That leaves a practical gap: researchers need networks detailed enough to test power-system methods, but cannot simply publish the real systems those methods are meant to help manage.

Synthetic grids address the gap by creating fictional networks designed to be electrically and structurally plausible without revealing facility-level information. The best-known large family, ACTIVSg, grows networks to match geographic and statistical properties of actual grids. EPIGRIDS was built differently. Its “KCL-only” construction method uses an optimization model to select corridors—the routes where lines connect substations—rather than growing the system to reproduce a chosen collection of graph statistics.

KCL stands for Kirchhoff’s current law: at a bus, the electricity flowing in must balance the electricity flowing out, accounting for generation and demand. The method’s first-stage network-flow model enforces that balance, but not the voltage law, which governs the relationship between voltage, current, and line impedance in an AC system. The builders then assign electrical parameters and refine the network until it supports a solved alternating-current, or AC, power flow. In short, the method chooses a plausible structure through an optimization problem, then checks whether the resulting electrical system can operate at a specified point.

The seven released cases cover different scales and geographies. The largest, Eastern, spans the footprint of 37 states and the District of Columbia and contains 78,484 buses. Western covers 11 states with 20,758 buses. Smaller cases represent Michigan, Ohio, and Indiana (MIOHIN), Texas, Florida, Wisconsin, and New England. Their modeled voltage levels reach as high as 765 kilovolts in Eastern and MIOHIN; voltage levels elsewhere reflect regional practice, topping out at 345 or 500 kilovolts.

(c) Western, 20,758 buses
(c) Western, 20,758 buses Source: Jonathan M. Snodgrass, Scott Greene

These are not seven independent creations. Texas, Florida, and MIOHIN are induced sub-networks of Eastern: they retain selected Eastern buses, branches, and generators, while ties to the rest of the system are removed and generation is adjusted. Texas here is a geographic portion of the Eastern model, not a model of ERCOT, the separate Texas interconnection. That family relationship is important when researchers count independent test systems or make claims about generalization.

The cases are distributed under the Creative Commons Attribution 4.0 license. Each comes in three familiar power-system formats: PowerWorld, MATPOWER, and PSS/E. The authors compared the exports and found that their networks and operating states agree closely, but the formats are not perfectly interchangeable in every detail. In particular, the MATPOWER export can encode generator limits and reactive loads differently; a user who treats it as exactly the same model may get different results.

Six larger cases also have a companion load series: hourly real and reactive demand at individual buses for 8,760 hours, or one year. That gives researchers a route beyond a single snapshot and toward testing how algorithms behave as demand changes over time. The load series maps to 95.9% to 100% of each corresponding case’s load in megawatts, according to the paper.

What They Found

The central validation result is practical: every released case solves an AC power flow from its stored operating point. AC power flow is the calculation that determines voltages, currents, and power flows while accounting for the alternating-current behavior of the network. The authors also report that the full single-outage contingency analysis—testing the network after the loss of each individual component—completes for every case.

EPIGRIDS spans five orders of network scale

Bus counts for all seven released cases, showing the range from a regional test system to an interconnection-scale model.

EPIGRIDS spans five orders of network scale
LabelValue
New England250 buses
Wisconsin1,664 buses
Florida5,658 buses
Texas7,336 buses
MIOHIN10,192 buses
Western20,758 buses
Eastern78,484 buses

The size range is unusually broad for a single release. At one end, New England has 250 buses; at the other, Eastern has 78,484. The set also includes a 1,664-bus Wisconsin model and intermediate regional cases of 5,658 to 20,758 buses. This lets researchers test methods at multiple scales without moving between unrelated repositories or data conventions.

The paper checks more than whether a solver returns an answer. PowerWorld’s AC solutions were independently compared with Newton power-flow solutions from PYPOWER using the MATPOWER files. The voltage differences were no more than 0.0075 per unit in every case except MIOHIN, where the largest difference was 0.035 per unit. In one 120-bus pocket, the tools settled on different generator reactive-power limits; applying the same limit statuses reduced the discrepancy to 0.0001 per unit. The episode is a reminder that solver behavior and operating limits can matter as much as the headline model size.

The authors also compare the structure of the interconnection-scale cases with real-grid references and with other synthetic cases built on the same footprints. With parallel circuits merged, EPIGRIDS’ Eastern network is 9% denser than the real Eastern Interconnection comparison; Western is 16% denser than its real-grid counterpart. The graph-statistics synthetic cases on those footprints are within 6% of the real comparisons and satisfy more of the published whole-case realism criteria examined by the authors. EPIGRIDS therefore adds methodological diversity, not a claim to be structurally superior on every measure.

Interconnection-scale EPIGRIDS are denser than real-grid references

Reported density difference for Eastern and Western cases, with parallel circuits merged.

Interconnection-scale EPIGRIDS are denser than real-grid references
LabelValue
Eastern9 % denser
Western16 % denser

There are operational caveats in the stored base cases. Some branches exceed their normal rating A: up to 140.7% in MIOHIN and 126.2% in Wisconsin. Several lower-voltage lines in Eastern and MIOHIN exceed even their post-contingency rating C while not monitored in the release files. Also, a large share of Eastern generators sit at their maximum reactive output under the paper’s test—53.7%, compared with 36.5% in ACTIVSg70k. These details do not invalidate the models, but they make clear why a benchmark’s precise operating state and assumptions should accompany any result.

The optimal power flow benchmark offers another test. Optimal power flow (OPF) seeks a least-cost or otherwise preferred operating point while respecting network and equipment constraints. Across seven PowerModels.jl formulations, every case except the New England base case and one of its 12 operating points solves in polar form. That near-complete result suggests the cases can support a meaningful range of OPF experiments, while the New England exceptions mark real limitations rather than a universal guarantee.

(a) New England, 250 buses
(a) New England, 250 buses Source: Jonathan M. Snodgrass, Scott Greene

Why This Changes Things

The contribution is not simply “more buses.” It is another recipe for making a synthetic grid. Modern machine-learning work often trains on variations of a small number of base systems. Models may then appear to generalize because they have seen many operating points, while still being tested on networks shaped by familiar assumptions. A second construction family gives researchers a sharper question: does a method learn power-system behavior, or does it lean on the topology and data patterns of one generator?

That question matters as AI tools are proposed for faster OPF, contingency screening, and other computationally demanding tasks. A surrogate can be useful only if its speed does not come at the cost of brittle performance when the grid looks different. EPIGRIDS creates an opportunity to test that transfer across construction methods. It does not prove that a model trained on one family will fail on another; it makes that possibility measurable.

The open, geolocated cases also offer a practical benefit for reproducibility. A published result tied to a downloadable model can be rerun, modified, and compared by researchers who do not have access to confidential utility data. Common formats lower the barrier to using the cases in existing toolchains, while the authors’ file-by-file comparison makes it easier to identify where an export changes assumptions.

The one-year load series extends that value from static networks to changing demand. Grid operations are not a single balance point: demand shifts by hour and place, and renewable generation adds further variability. Bus-level hourly loads give researchers a more realistic substrate for experiments on time-dependent optimization, forecasting, and learned approximations. The dataset does not itself provide a complete time series of every generation source or validate every possible operational scenario, but it opens a useful door.

(b) Wisconsin, 1,664 buses
(b) Wisconsin, 1,664 buses Source: Jonathan M. Snodgrass, Scott Greene

The geographic names could also mislead without the paper’s careful documentation. Texas, Florida, and MIOHIN share the Eastern network’s underlying construction and load snapshot. Their performance is valuable evidence about subnetwork behavior, but they should not be counted as three independent demonstrations that a method works on separately constructed grids. This provenance is exactly the kind of detail that benchmark users need—and that benchmark papers too often leave implicit.

The structural comparison is similarly instructive. “Realistic” is not one score. A network can match some aggregate graph properties and differ on others; it can be physically solvable while carrying unusual density or generator-limit patterns. By reporting these differences rather than smoothing them away, the paper helps users select cases that fit a question and interpret results in context.

What’s Next

The immediate next step is cross-family testing. Researchers can train an OPF surrogate or contingency classifier on one synthetic family, evaluate it on EPIGRIDS, and measure the loss in accuracy or reliability. They can also reverse the direction, or train on a mix. Such tests would show whether network-generation diversity is merely a dataset virtue or a decisive stress test for algorithms intended for real-world deployment.

There is also room to improve the models and their validation. The authors identify density differences, high reactive-limit participation, base-case overloads, and format-specific conventions. Future releases could make these issues easier to navigate through standardized metadata, more explicit monitoring assumptions, and additional operating points. The companion load series is a start; broader temporal data and complementary renewable or generator availability profiles would support richer studies of changing grid conditions.

The paper is a documentation and validation study, not a demonstration that EPIGRIDS reproduces every feature of an actual U.S. grid. The cases are synthetic; their construction involves assumptions, and three regional networks are cuts of the Eastern model. Nor does a successful benchmark guarantee that an algorithm will work on a utility’s confidential system. Those are limits to keep in view, not reasons to discount the release.

A resilient energy transition depends partly on tools that can plan and operate increasingly complex networks. Those tools need tests that are public, repeatable, and varied enough to expose hidden assumptions. EPIGRIDS supplies a substantial new set of test cases—and, more importantly, a different way of building them. The next advance will come when researchers use that difference to ask whether their algorithms can travel beyond the grids on which they learned to work.