An AI data center cut grid-frequency decline in half—without shutting down its servers

An AI data center cut grid-frequency decline in half—without shutting down its servers
100 MW Data center size simulated
Servers And Battery Share Power Support method
Computer Simulation Only Study type
50% frequency decline reduced

In a simulation, a 100-megawatt AI data center helped cut the grid’s fastest frequency decline by nearly half during a sudden power shortage. The result points to an intriguing possibility: the machines that make AI energy-hungry might also help keep electricity systems stable—if their power electronics and computing workloads are designed to cooperate.

The proposed controller coordinated two resources inside the facility: its servers, which could briefly use less power, and the batteries in its uninterruptible power supply (UPS). During a simulated 20 MW shortfall on a low-inertia grid, the data center’s maximum rate of change of frequency fell to 1.058 hertz per second, compared with 2.054 Hz/s under conventional grid-following control. The simulated frequency nadir—the lowest frequency reached—rose from 59.46 to 59.86 Hz (Zhang et al., 2026).

Those figures are encouraging, not a promise that every data center can deliver the same service. They come from time-domain simulations of a modeled facility, not a field trial, and they do not tell operators how much computation users would notice being curtailed or how battery wear would change. But they sharpen a useful shift in perspective: a large, controllable electricity load may be more than a problem the grid has to accommodate. It could become part of the grid’s response.

Fig. 1: Framework of a grid-connected AI data center.
Fig. 1: Framework of a grid-connected AI data center. Source: Xuechun Zhang, Zhiyi Zhao

The Science

Electricity systems have to keep supply and demand balanced moment by moment. When a large generator or transmission link suddenly disappears, the imbalance tends to pull grid frequency down. In many power systems, spinning generators slow their rotation and release stored kinetic energy, blunting the initial fall. As renewable generation and power-electronic devices take a larger role, the system may have less of that naturally available inertia.

A data center is usually understood as demand: it draws power to run servers, cooling and other equipment. Yet the facility’s interface to the grid is already built around power converters, and some server workloads can tolerate short-term adjustments. The question is whether those pieces can be controlled quickly enough—and in a coordinated way—to help during a disturbance.

The authors propose using grid-forming control, or GFM, at both ends of the data center’s back-to-back converter system. A converter is the equipment that changes electricity between forms, such as alternating current from the grid and direct current on the facility’s internal link. In GFM operation, a converter behaves more like a voltage source that helps establish local electrical conditions. This contrasts with grid-following control (GFL), which tracks an existing grid voltage and typically responds to measured frequency changes.

The distinction matters because conventional frequency response often depends on first measuring a frequency deviation and then issuing a power command. The paper’s approach uses the converter’s dynamics and the voltage of the internal DC link—the direct-current connection between conversion stages—to coordinate action. The grid-side converter supports the external grid; the load-side converter maintains a stable supply for the servers. A UPS battery connects to the same DC link.

Fig. 2: Diagram of the proposed GFM control scheme.
Fig. 2: Diagram of the proposed GFM control scheme. Source: Xuechun Zhang, Zhiyi Zhao

The third participant is the IT load itself. Servers can reduce power through power capping: software or hardware limits on processor operation, often implemented by adjusting clock speed and voltage. That is distinct from stopping a job or moving it elsewhere. The paper focuses on this faster form of flexibility, because power capping can respond on millisecond-to-second timescales, while task scheduling, switching servers on or off, and workload migration generally take longer.

The researchers also model the fact that a data center is not one uniform machine. Training, fine-tuning and inference tasks differ in how much power can be reduced and how quickly. They aggregate these diverse server responses into a first-order model—one that represents power changes as a response that approaches a new target over time. Under the assumptions used for the test case, the aggregate IT-load response has an equivalent time constant of about 0.2 seconds.

What They Found

The test system combines a 100 MW AI data center and a 100 MW wind farm connected to a 200 MVA low-inertia grid. The data center’s baseline power is divided among 70 MW of IT demand, 20 MW for cooling and 10 MW for auxiliary systems. For the fast response studied, the authors treat cooling and auxiliary demand as effectively fixed, so the controllable response comes mainly from the servers and UPS storage.

At two seconds into the simulation, the external grid experiences a sustained 20 MW power deficit. The data center’s grid-side converter responds to the disturbance, while changes in DC-link voltage prompt both the IT loads and energy storage to adjust. The power-sharing controllers are tuned for a target in which IT loads and storage each ultimately contribute half of the response. The battery acts more quickly at first; the server load catches up as its power-capping response unfolds.

Fig. 4: Simulation results of the proposed GFM-AIDC.
Fig. 4: Simulation results of the proposed GFM-AIDC. Source: Xuechun Zhang, Zhiyi Zhao

That timing is central to the idea. A battery can provide an immediate burst, while server demand can contribute without requiring the facility to stop operating. In the model, the fast energy-storage response bridges the interval before the slower aggregate IT response is fully delivered. The control system is designed to share the task through the DC-link voltage rather than through an additional external command or communications link.

The comparison with other control strategies shows the largest difference in the initial frequency dynamics. Under classic GFL control, the maximum rate of change of frequency (RoCoF) is 2.054 Hz/s; with GFL plus fast frequency response (FFR), it is 2.057 Hz/s. Under the proposed GFM strategy it falls to 1.058 Hz/s. RoCoF describes how quickly frequency changes, and is important because a steep fall can leave less time for protective systems and other resources to respond.

The frequency nadir also improves. The paper reports 59.46 Hz for classic GFL, 59.70 Hz with GFL plus FFR, and 59.86 Hz with the proposed GFM scheme. In a 60 Hz system, the nadir is the lowest frequency reached after the disturbance; a higher nadir means a smaller simulated dip. The FFR case improves that lowest point, but its maximum RoCoF remains about the same as classic GFL. The authors interpret this contrast as evidence that GFM offers support during the inertial stage, not only a later response after frequency deviation has been measured.

Grid response in the 100 MW data-center simulation

Maximum rate of change of frequency and frequency nadir under the three control strategies reported in Table IV.

Grid response in the 100 MW data-center simulation
LabelValue
Classic GFL — maximum RoCoF2.0542 Hz/s
GFL with FFR — maximum RoCoF2.057 Hz/s
Proposed GFM — maximum RoCoF1.058 Hz/s
Classic GFL — frequency nadir59.46 Hz/s
GFL with FFR — frequency nadir59.7 Hz/s
Proposed GFM — frequency nadir59.86 Hz/s

These are system-level simulation results, not direct measurements from an operating data center. They depend on the model’s converter settings, task flexibility assumptions, storage capacity and grid conditions. Still, the comparison establishes a specific engineering proposition: a data center can combine converter behavior, battery response and flexible computing demand in a single control scheme, and that combination can improve both reported frequency measures in this modeled event.

Why This Changes Things

The scale of the issue is growing. Data centers are large new loads, and AI facilities can concentrate substantial demand in a single location. The paper cites a projection that global data-center electricity use could reach 950 terawatt-hours by 2030 (IEA, 2026). The number is a projection, not a guaranteed outcome, but it captures why utilities and planners are paying closer attention to when and where large computing loads connect.

Much of the public debate frames that growth as a contest: more computation means more electricity demand, and more demand means more pressure on grids. This paper does not dispute the first half. Instead, it asks whether a portion of that demand can be made responsive. A facility that trims or shifts a fraction of its power during a grid emergency could help reduce the need for other fast reserves, provided the service is reliable and the computing consequences are acceptable.

The word “flexible” needs care here. Not every AI job can pause without consequence, and a power cap may slow computation rather than make the energy requirement disappear. The authors’ task model assigns different available reductions: 50% for training, 25% for fine-tuning and 10% for the modeled inference category. Those are assumptions drawn from prior sources for this simulation, not universal guarantees for all workloads. The model also assumes that half of inference power comes from deferrable tasks.

Fast power flexibility varies by computing task

Maximum available power-reduction ratios assigned in the paper's task model.

Fast power flexibility varies by computing task
LabelValue
Training50 %
Fine-tuning25 %
Inference (deferrable portion)10 %

The hierarchy of options matters for operations. Power capping is listed at milliseconds to seconds; task scheduling at seconds; server activation at seconds to minutes; and moving work to another data center at minutes to hours. That makes capping the relevant first lever for a fast grid disturbance. Slower measures could still matter for sustained constraints or planned demand management, but this study does not evaluate them as part of the immediate GFM response.

Ways to adjust data-center demand

Response timescales listed by the paper for four IT-load flexibility methods.

Ways to adjust data-center demand
LabelValue
Power capping1 ms–s
Task scheduling2 ms–s
Server activation3 ms–s
Load migration4 ms–s

The approach also makes use of equipment data centers already need. UPS batteries are installed to protect computing from outages, and power converters are essential to delivering electricity to servers. If these systems can provide grid services without undermining their primary purpose, the facility might become a more useful grid partner without relying entirely on new dedicated infrastructure.

But the benefit is not free. A battery that repeatedly charges and discharges may age faster, and reducing server power can affect throughput, latency or service commitments. The study’s target of equal power sharing is a control design choice, not a proven economic optimum. Its conclusion explicitly identifies the trade-off between IT performance penalties and UPS battery degradation as a subject for future work.

What's Next

The next step is to take the control strategy beyond a modeled 100 MW facility. Field demonstrations would need to test converter interactions, actual server power-capping behavior, protection systems and grid-code requirements under realistic operating conditions. They would also need to establish how much load is genuinely available at any moment: a data center’s flexibility can vary with workload mix, customer commitments, temperature, battery state of charge and the facility’s need to retain backup capacity.

The study’s aggregated response model is useful because it turns many different servers into a tractable representation. Yet aggregation can hide awkward details. Real workloads may not respond as a smooth first-order lag, and different hardware, scheduling systems and service-level agreements may limit how power can be adjusted. Validation against measurements from operating servers would show whether the estimated 0.2-second response adequately describes facilities beyond the specific task assumptions in this case.

Another open question is how to divide the work between battery and computation. A higher battery share could deliver a quicker response but potentially increase cycling; a larger IT share might preserve battery life but impose greater performance costs. The paper derives a way to set the target sharing ratio through controller gains, but it does not optimize that ratio against electricity-market payments, battery replacement costs, or the value of uninterrupted computing. Those are economic and operational questions as much as control-engineering ones.

Finally, the modeled event is a sustained 20 MW shortfall in one test grid. Grid disturbances differ in duration, location and cause. A controller that performs well in one scenario must still be assessed for faults, recovery behavior, interactions with renewable generation and other grid-forming resources, and the possibility that many facilities respond at once. Coordinated participation at scale would require clear rules about performance verification and the amount of capacity each data center can safely offer.

The broader possibility is nonetheless striking. AI’s electricity demand is rising, but demand need not be entirely passive. If future trials confirm that servers can provide a fast, predictable response without unacceptable costs to users or batteries, data centers could help steady the same grids they are making more heavily used. That would not erase their energy footprint. It would give grid planners a new way to work with it.