Averages can hide the grid’s weakest links

Averages can hide the grid’s weakest links
IEEE 39-Bus Grid Test system
50% GFM Penetration Inverter share tested
Placement Matters More Than Averages Key finding
0.21 Hz/S max local RoCoF
104 MHz local nadir variation
89% averaging hid variation

At 50% grid-forming inverter penetration, a system-wide frequency average concealed 89% of the placement-driven variation in local frequency nadir. The implication is unsettling and useful: a grid can look steady as a whole while the response at a particular location changes markedly depending on where its inverters are connected. In a model of the IEEE 39-bus system, changing placement at a fixed inverter share shifted the worst local frequency nadir by as much as 104 millihertz and the maximum local rate of change of frequency by 0.21 hertz per second (Alfailkawi et al., 2026).

Those are not predictions of imminent blackouts. They are evidence that the usual system-wide scorecard can miss important differences between candidate designs. As wind and solar replace conventional generators, grid planners need to know not just how much inverter capability is present, but where it sits—and whether the metric they use can see the vulnerable corners of the network.

The Science

Electric grids must keep frequency close to its nominal value as supply and demand shift. In much of North America, that nominal frequency is 60 hertz. A sudden load increase draws on the system and tends to pull frequency down; the lowest point reached is the frequency nadir. The rate of change of frequency, or RoCoF, measures how quickly frequency moves after a disturbance. Both measures matter: a deep nadir can trigger protective systems, while a rapid change can challenge equipment and controls.

Traditional grids relied heavily on synchronous generators: large rotating machines whose physical inertia slows the initial frequency response and whose governors adjust mechanical power. Wind and solar plants connect through power electronics, however, and do not inherently behave like spinning machines. Grid-forming inverters (GFMs) are controlled to establish a voltage and frequency reference and respond to disturbances. They are one proposed way to support grid stability as inverter-based resources grow. The question is not simply whether GFMs help, but how their locations and interactions shape the response across the network.

Alfailkawi, Trujillo, and Hodge examined that question in a modified IEEE 39-bus test system, a standard network model with ten candidate generator sites. They considered every possible assignment of synchronous generator (SG) or GFM at those sites: 1,024 configurations in total. For each configuration, they applied load increases separately at eligible load buses, then retained the worst response across disturbance locations for each metric.

The exhaustive search was possible because the team used a reduced-order model. It represents generator dynamics and the electrical connections among them while eliminating many non-generator network nodes mathematically, a technique called Kron reduction. The resulting model is linear and computationally efficient. It lets the researchers scan configurations that would be expensive to simulate in detailed, nonlinear models, but it also means the results are a screening study rather than a complete account of real-grid behavior.

The researchers compared local frequency measures with an aggregate measure: a device-rating-weighted average of generator frequencies. This resembles the system-wide perspective often used in conventional frequency analysis. For local metrics, they examined the worst frequency nadir across generator buses and the largest absolute RoCoF. RoCoF was measured over a 500-millisecond window, and the study used 1 hertz per second as a reference threshold consistent with Irish grid-code practice.

(a)
(a) Source: Fatma Alfailkawi, Marena Trujillo

What They Found

Placement mattered most when the researchers looked locally. At fixed GFM penetration, the largest best-to-worst difference in local nadir was 104 mHz, at 50% GFM. The largest spread in maximum local RoCoF was 0.21 Hz/s, at 70% GFM. These figures describe differences among placements, not the absolute frequency change in every configuration. Still, they show that identical technology shares can produce meaningfully different worst-case local responses.

The aggregate metric compressed that spread. At 50% GFM, aggregate-frequency assessment reduced the apparent across-placement variation by 89% for nadir and 88% for RoCoF. Put another way, the placements that look relatively similar when averaged can be much less similar at individual buses. The comparison does not establish that every aggregate metric is useless; it shows that averaging can suppress the very location-specific differences the study set out to measure.

Placement spread in local frequency response

Maximum reported best-to-worst placement spread at fixed GFM penetration, as described in the abstract and results.

Placement spread in local frequency response
LabelValue
Local nadir spread104 mHz
Local RoCoF spread0.21 mHz

The pattern also changed with penetration. The median aggregate nadir improved as the number of GFMs increased, but aggregate RoCoF did not move monotonically. Local behavior did not simply mirror those aggregate trends. At 50% GFM, the authors report a notable reduction in the median local bus nadir, making this a potentially important mix in their modeled system. That is a result for this benchmark and these device assumptions, not a universal rule that half-inverter grids are inherently worse.

One location stood out. Bus 38 was consistently an unfavorable place to assign a GFM for local nadir across the tested GFM counts; maximum local RoCoF there also became more pronounced at higher GFM penetrations. In the model, changing bus 38 from SG to GFM persistently worsened the worst-case local nadir and RoCoF. Why that site behaves this way remains an open question. Its significance may lie in the network’s electrical structure and the way device dynamics interact with that structure, not in a general property of the number 38.

The disturbance locations that produced the most severe local responses were also strikingly persistent: buses 29, 9, and 20 remained dominant across the SG/GFM configurations. By contrast, the locations that set the worst aggregate response changed with placement and inverter count. This suggests a practical distinction: some local weak spots may be structurally important across many technology mixes, while the system-wide average can shift its apparent point of concern as the mix changes.

(a)
(a) Source: Fatma Alfailkawi, Marena Trujillo

The authors also used the model’s linearity to estimate how large a load step could be before the local nadir or RoCoF reached a chosen threshold. Because this relies on proportional scaling in a linear model, it is a screening margin, not a physical guarantee of how a real grid would withstand a large event. The paper’s main point is that this estimated tolerance depends on inverter placement, not only on total GFM count.

How much aggregation masks at 50% GFM

Reduction in apparent placement variation when using aggregate rather than local frequency assessment.

How much aggregation masks at 50% GFM
LabelValue
Nadir variation masked89 %
RoCoF variation masked88 %

Why This Changes Things

A frequency average is attractive because it reduces a complicated network to a single trace. In a system dominated by synchronous machines, their strongly coupled, inertia-driven response can make that summary useful. But power-electronic controls can act quickly and unevenly across the network. When different regions respond differently, averaging can make a local excursion disappear into the system-wide picture.

That matters because the grid is not experienced as an abstract average. Protection equipment, generators, and large loads connect at specific locations. A local frequency dip or rapid change may be consequential even when the weighted average remains within a planning target. The study therefore adds a placement-sensitive reason to examine local frequency performance alongside traditional aggregate indicators—not to discard the latter, but to avoid treating it as a complete description.

The transition is moving from theory into planning. The paper points to operating examples of GFMs in renewable-rich island grids and battery projects, and to Ireland’s plans for GFM requirements. Meanwhile, inverter-connected generation is expected to carry a growing share of electricity. Decisions made now about interconnection locations and control requirements could shape how robustly future systems respond to disturbances.

The results also complicate a simple “more is better” narrative. The median aggregate nadir improved as GFM count rose, yet local frequency outcomes could worsen at particular buses and varied among placements. A technology can support the system in one broad sense while creating or exposing a local weakness in another. That is not an argument against GFMs. It is an argument for treating them as networked components whose value depends partly on where they are placed and how they are controlled.

This distinction is especially relevant as electricity demand becomes more geographically concentrated. The paper discusses large, frequency-sensitive loads such as data centers, and cites a reported power reduction of about 1.5 gigawatts following a short voltage disturbance. Such events can create rapid, localized imbalances. A planning method that sees only the aggregate response may be poorly equipped to identify where those imbalances and fast controls interact most sharply.

(a)
(a) Source: Fatma Alfailkawi, Marena Trujillo

What’s Next

The researchers are careful about what their model can establish. It uses a reduced-order, linear representation, assumes stability beyond the modeled dynamics, and holds device parameters constant across assignments. The network is a modified benchmark rather than a real operating grid. The study does not include grid-following inverter dynamics or voltage behavior, and it does not fully capture nonlinearities that can matter during large disturbances. Its results reveal sensitivity and guide where closer analysis may be worthwhile; they do not certify a particular placement as safe or unsafe in practice.

The next step is validation. The authors propose examining selected configurations with higher-order models that include nonlinear dynamics, voltage effects, and additional inverter types. The repeatedly critical disturbance buses and the striking bus 38 result offer candidates for that deeper investigation. Researchers will also need to explain the mechanisms: which network features make some placements resilient and others vulnerable, and whether those features can be translated into planning rules that work beyond this one test system.

For grid operators, the near-term lesson is methodological. Compare placements at the same inverter share, test disturbances at multiple locations, and report local as well as aggregate frequency measures. The study does not offer a universal placement recipe, but it shows why a single frequency trace can be too reassuring. As grids become more diverse and their controls faster, stability will depend not only on how much capability the system has, but on whether that capability is in the right places—and whether our measurements are looking there.