The grid plans matched on cost—and disagreed on where to build
A 1.2% difference in total cost sounds like proof that three grid-planning models tell the same story. But when researchers looked beneath the totals, they found very different maps of where power plants, batteries and transmission lines should go. In Germany, one simplified model put 10.7 gigawatts of onshore wind in a zone where a physics-based model put 4.2 GW. The first model treated nearby wind farms as if they could use separate routes to market. On a real grid, they compete for some of the same wires.
That distinction matters. Governments, utilities and grid operators use capacity-expansion models to decide what to build over the coming decades. If a model gets the national bill approximately right but directs investment to the wrong locations, the real system may need extra lines, different generation or other fixes before it can operate reliably. The finding from Lara Booth, Shiva Madadkhani, Ruaridh Macdonald and Priya L. Donti is not that simplified models are useless. It is that a reassuring system-wide total can hide a consequential local mismatch.
Total modeled system cost
System cost by transmission formulation. Germany and ERCOT are shown in separate panels because the reported currencies differ.
| Label | Value |
|---|---|
| Germany · Transport | 38.67 billion € |
| Germany · DCOPF | 39.13 billion € |
| Germany · ACOPF | 38.66 billion € |
| ERCOT · Transport | 19.25 billion € |
| ERCOT · DCOPF | 19.32 billion € |
| ERCOT · ACOPF | 19.27 billion € |
The team compared three ways to represent electricity moving through a grid: a simple “transport” model, a more electrical DC model, and a full alternating-current model. Across 20-zone representations of Germany and Texas, total costs and emissions stayed close. Yet the models made notably different choices about the location and amount of new generation, battery storage and transmission. The most physical model also planned for substantially more battery power capacity, in part because batteries can help provide the reactive power needed to keep voltages within bounds.
The Science
A capacity-expansion model asks a deceptively simple question: given expected demand, technology costs and resource availability, what combination of power plants, storage and network upgrades will meet electricity needs at the lowest modeled cost? To answer it, the model must represent not just what is built, but how the resulting system operates over time. A plant in a windy region is useful only if its power can reach customers when it is generated.
That last step is where the models differ. The transport model treats the grid rather like a set of pipes: power can travel on any route with enough remaining capacity. DC optimal power flow (DCOPF) adds an important electrical rule: flows divide across connected lines according to their impedances, a measure of how difficult it is for electricity to pass along each line. But DCOPF still simplifies the physics. It does not explicitly represent voltage magnitudes or reactive power.
Alternating-current optimal power flow (ACOPF) represents those features as well. Reactive power does not deliver energy to a light bulb, but it helps maintain the voltage needed for the grid to function. Generators and other equipment must supply or absorb it. ACOPF therefore captures additional operating constraints, including limits on voltage and the interaction between active power—the energy that does useful work—and reactive power. Those extra constraints make it a more realistic representation, but also make its equations nonlinear and nonconvex, and much harder to solve at planning scale.
The authors extended GenX, an open-source capacity-expansion model, to include ACOPF. They compared it with the transport and DCOPF versions using 20-zone models of Germany and the Electric Reliability Council of Texas (ERCOT). Each model co-optimized generation, storage and transmission investment alongside operations. To make the AC calculations manageable, the team represented the year using 20 weighted representative periods for Germany and 32 for ERCOT, rather than solving every hour in the full year. The underlying input data came from 2023 for Germany and 2022 for Texas.
The cases were not identical replicas of current grids. The analysis assumed no existing generation or storage capacity, so it could compare new investment decisions cleanly, but it retained and allowed expansion of the existing transmission network. It included different technology menus for the two regions: for example, Germany could build offshore wind and biomass, while ERCOT could build coal. The researchers also capped new thermal capacity at 5 GW per zone in ERCOT, because unconstrained results would have placed roughly 14 GW of new gas capacity in each of Houston and Dallas—an outcome they considered inconsistent with siting practice and the development pipeline.
The two systems create different tests for transmission planning. Germany’s wind resources are strongest in the north, away from major demand centers to the west and south. Texas has large concentrations of demand around Dallas and Houston, but its renewable resources and export routes are distributed differently. The authors’ maps show this geography zone by zone: resource quality, demand and the existing network shape the options available to the model.
What They Found
At the broadest level, the models agreed remarkably well. Germany’s total modeled costs ranged from €38.66 billion under ACOPF to €39.13 billion under DCOPF. ERCOT’s ranged from $19.25 billion to $19.32 billion. Emissions also stayed close: 59.6–62.5 million tonnes of CO₂ in Germany and 107.9–110.5 million tonnes in ERCOT. These are not identical outcomes, but the aggregate differences are small compared with the differences in specific investments.
Emissions remain close across formulations
Total modeled CO₂ emissions in Germany and ERCOT, by transmission formulation.
| Label | Value |
|---|---|
| Germany · Transport | 60.3 Mt CO₂ |
| Germany · DCOPF | 62.5 Mt CO₂ |
| Germany · ACOPF | 59.6 Mt CO₂ |
| ERCOT · Transport | 109.2 Mt CO₂ |
| ERCOT · DCOPF | 110.5 Mt CO₂ |
| ERCOT · ACOPF | 107.9 Mt CO₂ |
The gap appears when the question changes from “How much capacity?” to “Where does it go?” In Germany, total installed capacity under the transport and DCOPF models was only 2.1% and 1.2% different from ACOPF. But across all zone-and-technology combinations, the absolute differences summed to 35.9% and 31.8% of ACOPF’s total capacity. In other words, overbuilding in one place can cancel underbuilding elsewhere in the national sum. The median zone’s total capacity differed from ACOPF by 37.5% under transport and 12.0% under DCOPF.
The corresponding median zonal differences in ERCOT were smaller, but still meaningful: 10.8% under transport and 8.7% under DCOPF. Annual generation showed a similar pattern. National totals were within about 1% across formulations, while in Germany the median zone’s generation differed from ACOPF by 29.1% under transport and 22.6% under DCOPF. One zone generated 166% more under DCOPF than under ACOPF. The set of technologies chosen in each zone was mostly stable; the more striking variation was how much of each technology was built and operated there.
The German wind example makes the physics visible. Zone 5 has strong onshore wind, and its hourly output is correlated with offshore wind in neighboring zone 16 (r=0.67). The transport formulation built 10.7 GW of onshore wind in zone 5. DCOPF built 2.0 GW, while ACOPF built 4.2 GW. Why? In the transport model, the two sources do not compete for the same transmission capacity. In the electrical models, power divides across parallel paths, so some of zone 5’s output flows through the routes that also carry zone 16’s offshore wind to customers.
That competition matters most when the wind farms produce together. The lines leaving the offshore hub are among the most heavily used in the German network; under ACOPF, they were above 80% of rated capacity in around 40% of hours. The simplified transport model, by assigning flows along eligible routes without the same electrical sharing rules, can make a crowded corridor look more available than it is. That encourages investment in generation whose output may be difficult to deliver during the very hours it is most abundant.
The choices also change the network itself. ACOPF added 34.2 gigavolt-amperes (GVA) of transmission capacity in Germany, compared with 30.3 GVA under transport and 31.2 GVA under DCOPF. GVA measures apparent power capacity, encompassing both active and reactive power. Of the 14 German lines reinforced by at least one formulation, transport differed from ACOPF on nine and DCOPF on eight; several lines were reinforced in one model but not another. In ERCOT, total transmission additions were more similar, and reinforcement limits often determined which lines reached their maximum capacity.
Batteries tell another part of the story. In Germany, ACOPF chose 16.6 GW of battery power capacity, compared with 7.3 GW under transport and 8.1 GW under DCOPF. But the ACOPF batteries had a shorter average duration: 1.60 hours, versus about 2.9 hours in the simplified models. In ERCOT, battery power capacity was 2.6 GW under ACOPF and 1.6 GW under either approximation; duration was 1.25 hours under ACOPF and around 1.6 hours in the other models.
ACOPF selects more battery power capacity
Installed battery power capacity in each case; note that Germany and ERCOT differ substantially in scale.
| Label | Value |
|---|---|
| Germany · Transport | 7.3 GW |
| Germany · DCOPF | 8.1 GW |
| Germany · ACOPF | 16.6 GW |
| ERCOT · Transport | 1.6 GW |
| ERCOT · DCOPF | 1.6 GW |
| ERCOT · ACOPF | 2.6 GW |
A battery is not only a container for energy shifting from sunny afternoons to evening peaks. Depending on its inverter and grid connection, it can also supply reactive power that supports voltage. Under the study’s baseline assumptions, ACOPF therefore found value in more battery power capacity, even though the extra power capability did not translate into proportionally more stored energy. This result depends on the model’s assumptions about which technologies can provide reactive support and how much they can provide; it should not be read as a universal forecast that every grid needs the same battery design.
Why This Changes Things
The central lesson is about the difference between a good total and a good plan. National cost and emissions are useful indicators, but they do not show whether a particular region will need a new line, whether a renewable project will face curtailment, or whether local grid support will be available. Those details affect permitting, investment, reliability and the distribution of economic benefits. A plan that points generation toward a location with abundant wind but constrained export routes can look efficient in an abstract model and become expensive to implement.
This matters more as electricity systems change. Wind and solar are often built where the resource is strongest, rather than close to demand. Electrification, data centers and other large loads are also changing the geography and timing of consumption. Meanwhile, batteries are becoming more common and can provide several grid services, not just energy storage. The more the system depends on diverse resources connected across long distances, the more consequential it becomes to understand how those resources share the network.
The results also show why “more realistic” does not automatically mean “always better for every question.” ACOPF is computationally demanding. A planning team may need to test many scenarios—different demand growth, fuel prices, weather years, technology costs and policy choices. If each run takes too long, analysts may explore fewer possibilities or work at coarser spatial and temporal resolution. A faster model that gets the broad picture right can still be valuable, provided users know where its blind spots lie.
The paper offers a practical direction: identify the effects that matter most and find ways to represent them in simpler models. For example, a planner might add constraints that capture competition for shared transmission corridors, or incorporate targeted requirements for reactive-power support. Such methods could preserve much of the speed of transport or DC models without pretending that every line is an independent pipe. The study does not establish a single universal correction; it shows where corrections may be worth investigating.
The contrast between Germany and ERCOT is useful here. Germany’s offshore wind hub and north-to-south resource geography make power-flow representation particularly important for some siting and transmission decisions. ERCOT’s demand centers and line-reinforcement limits shape a different pattern, with closer agreement in several outcomes. That is a reminder that no one benchmark can tell planners how much simplified physics matters everywhere. The impact depends on network structure, resource geography, demand and investment limits.
What’s Next
The results come with important boundaries. These are 20-zone models, not detailed representations of every bus and line in either grid. They use one weather year per region and a reduced set of representative operating periods. They assume greenfield generation and storage investment, while retaining the existing transmission network. Technology costs differ between the German and U.S. datasets, so the absolute investment levels should not be compared across regions as if they were produced under a single shared set of assumptions.
There is another important qualification: the approximate models’ investment decisions were evaluated using their own transmission representations, not subsequently run through a full AC power-flow check. So the paper demonstrates that the formulations choose different plans; it does not quantify, for every approximate plan, exactly how much remedial investment would be needed to make it operate under full AC physics. The authors’ results are a planning comparison, not a claim that each simplified plan is necessarily infeasible.
Future work can test whether targeted network constraints improve simplified models across more regions, more weather years and more detailed networks. It can also probe the assumptions behind reactive capability: which generators, inverters and storage systems can provide it, and under what conditions? Another question is how these effects shift as planners add flexible demand, new transmission technologies, or different forms of long-duration storage.
For now, the study delivers a useful warning and a hopeful one. The warning: a model can get the bill right while misplacing the infrastructure. The hopeful part: the mismatches are not invisible. By tracing them to particular corridors, resources and grid services, planners can focus expensive high-fidelity analysis where it is most valuable—and build faster tools that are less likely to mistake a plausible total for a reliable map.