← News
Tech for Good Tech for Good Frontiers

The island-grid paradox: renewables need a grid that can stand on its own

The island-grid paradox: renewables need a grid that can stand on its own
Grid-Forming Converters Technology reviewed
Stronger Grid Stability Main benefit
Standards And Coordination Remaining hurdles

A single generator can be a big enough part of an island’s electricity supply to threaten the whole system when it trips. That is the island-grid paradox: places with abundant wind and sun may be especially vulnerable to relying on them, because their small, isolated grids have fewer backup generators and less ability to borrow support from elsewhere.

The report by Anup Joshi and colleagues asks whether grid-forming converters can help solve that problem. These power-electronic devices can set the grid’s voltage and frequency, rather than merely matching a signal already established by other generators. The authors argue that they could supply some of the stabilizing services of conventional spinning machines, making high-renewable operation more practical. But the report is equally clear that technology alone will not do it. Controls must work together, protection systems must be coordinated, and grid rules must specify what converters are expected to provide.

The stakes extend beyond islands. Island power systems compress into a small area many of the challenges that larger grids will face as wind, solar and batteries displace conventional generators. They can serve as early proving grounds for a renewable-heavy future—but, as the report’s case studies show, they also make the consequences of poor design and coordination harder to ignore.

Peak demand varies sharply across island systems

Maximum demand values reported for the five largest island systems in the paper’s comparison table.

Peak demand varies sharply across island systems
LabelValue
Canary Islands1,372 MW
Balearic Islands1,286 MW
Hawaii1,102 MW
Jeju Island1,000 MW
Crete650 MW

The Science

An electricity grid must keep supply and demand in balance from moment to moment. When a generator suddenly disconnects, the system loses supply. In a conventional grid, the heavy rotating parts of synchronous generators resist the resulting frequency change, buying time for controls to respond. This buffering effect is called inertia. Island systems tend to have less of it, and the loss of a single unit can be large relative to the total system.

The report’s comparison table lists peak demand from 48 megawatts on the Faroe Islands to 1,372 megawatts in the Canary Islands. These systems differ greatly in size and generation mix, but share a defining constraint: limited interconnection. They cannot draw freely on a vast neighboring network if a local plant fails or renewable output drops. Many also depend on a small number of generating units, so an outage can have an outsized effect.

Wind and solar power usually connect through converters—electronic interfaces that turn their output into electricity compatible with the grid. A conventional grid-following (GFL) converter synchronizes itself to an existing voltage waveform. That works well when the surrounding grid is strong. But in a weak grid, the waveform can shift or distort, and the converter’s efforts to follow it may contribute to instability.

A grid-forming (GFM) converter takes a different role: it can establish a voltage waveform and help set frequency. With appropriate control and an energy source behind it, a GFM converter can respond quickly to changes in power, regulate voltage, and support a system’s strength. The report describes these functions as potential ways to replace or supplement services traditionally associated with synchronous machines—not as a claim that every converter automatically provides them.

“Grid strength” refers in part to how firmly voltage holds when the system is disturbed. One common measure is the short-circuit ratio (SCR), which relates the strength of the network at a connection point to the capacity of the equipment connected there. A low SCR signals a weak grid, with limited fault current and greater sensitivity to disturbances. In such conditions, converter controls that behave well in a large network may interact poorly with one another or with the grid itself.

Figure 3: Comparison of frequency excursions between interconnected and islanded power systems. Figure from [107].
Figure 3: Comparison of frequency excursions between interconnected and islanded power systems. Figure from [107]. Source: Anup Joshi, Luis A. Garcia-Reyes

The report reviews several kinds of stability problem. Frequency stability concerns keeping frequency within safe bounds after a mismatch between generation and demand. Voltage stability concerns maintaining acceptable voltage, particularly when the system lacks enough reactive-power support. Converter-driven stability concerns oscillations or loss of synchronism caused by interactions among power-electronic controls and network components. Resonance and local electromechanical behavior matter too, although the report identifies frequency and converter-driven stability as especially urgent in island systems with high shares of inverter-based resources.

The authors also review how engineers test stability. Time-domain simulations follow a system through a disturbance, while small-signal analysis asks whether small deviations around an operating point grow or fade. Frequency-domain methods examine how devices respond across different frequencies. No single method captures every risk: the report recommends combining approaches, with detailed electromagnetic-transient studies where fast converter interactions are important and system-level analysis for broader dynamics.

What They Found

The strongest practical example comes from Suðuroy in the Faroe Islands. The report cites operation with 100% wind generation supported by a 6.3-megawatt, 7.5-megawatt-hour battery using grid-forming control and an 8-megavolt-ampere synchronous condenser. A synchronous condenser is a rotating machine that can provide voltage support and short-circuit strength without serving as a conventional fuel-burning generator. The example suggests that a battery and power electronics can help sustain a system that has no conventional generation online—but it does not mean that a grid becomes immune to large disturbances. The report emphasizes that operation remains sensitive to such events and requires careful control tuning.

Figure 4: Measured response in Suðuroy (Faroe Islands) during a suddenly drop of 100% wind operation with BESS and synchronous condenser. a) Frequency and, b) Wind Plant (PO) and Battery System (BS) active power during a loss of full production within 15 s. Figure from [112].
Figure 4: Measured response in Suðuroy (Faroe Islands) during a suddenly drop of 100% wind operation with BESS and synchronous condenser. a) Frequency and, b) Wind Plant (PO) and Battery System (BS) active power during a loss of full production within 15 s. Figure from [112]. Source: Anup Joshi, Luis A. Garcia-Reyes

The report also describes a 1-hertz oscillation in Kauai, Hawaii, traced to the power plant controller of a grid-forming plant. The detail is important because it complicates the appealing idea that grid-forming automatically means grid-stabilizing. A converter can actively shape system behavior, but its control settings can also excite oscillations or conflict with other devices. The relevant question is not simply whether a grid has GFM equipment, but whether its many controls have been designed and tested as a coordinated system.

For frequency stability, the report lays out a familiar sequence: an immediate response, primary control from generators and loads, then secondary control to restore frequency. In island grids, the first seconds can be unforgiving. If the remaining generators cannot ramp quickly enough, frequency may fall to thresholds that trigger under-frequency load shedding (UFLS)—automatic disconnection of selected demand to prevent a wider collapse. The report notes that UFLS plays a more active role on islands, and that its settings must account for fast battery response. Poor coordination could shed customers unnecessarily, or act too late to arrest a frequency decline.

The report’s review also highlights the difficulty that phase-locked loops (PLLs) can face in weak grids. A PLL is a control mechanism that estimates the phase and frequency of the grid voltage so a converter can synchronize with it. In low-SCR conditions, the synchronization process can interact with grid impedance and contribute to instability. Possible responses include retuning controls, reducing controller gains, strengthening the network with devices such as synchronous condensers, or using alternative synchronization and grid-forming approaches.

A small-signal case study in the report compares a weak-grid configuration with and without a GFM voltage-source converter. Its stated conclusion is that the GFM converter improves small-signal stability. The material supplied with the report does not include the numerical modal results or plot values, so the size of that improvement cannot be quantified here. That distinction matters: the study supports the proposed mechanism, but the available description does not establish a universal performance gain across systems.

Smaller island systems, same stability challenge

Maximum demand values for the four smaller island systems listed in the report’s comparison table.

Smaller island systems, same stability challenge
LabelValue
Guadeloupe256 MW
Madeira150 MW
Azores76 MW
Faroe Island48 MW

Why This Changes Things

The island systems listed in the report range from a 48 MW peak demand in the Faroe Islands to 1,372 MW in the Canary Islands. A single solution cannot be assumed to fit all of them. Their fuels, network designs, storage resources and links to mainland systems differ; some have high-voltage direct-current (HVDC) connections, while others depend more heavily on local generation. Still, the shared constraint—limited outside support—makes the consequences of instability immediate.

That makes islands a useful test bed for the broader energy transition. A large interconnected grid can smooth variable wind and solar across geography and draw on many generators. An island often cannot. Engineering a reliable system under those conditions can reveal which combinations of storage, control, conventional machines and interconnections are necessary before similar questions arise at greater scale. At the same time, the report cautions against treating islands as miniature versions of continental grids: their operating needs and restoration pathways are distinct.

GFM technology matters because it changes the converter’s role. Rather than waiting for a voltage and frequency reference, it can contribute to creating one. That opens a route for battery storage and renewable generation to provide fast frequency response, voltage regulation and black-start support—the ability to help restart a grid after a blackout. In principle, this can reduce dependence on imported fossil fuels, which are expensive and logistically difficult to deliver to remote islands. The report presents GFM as an enabler, not a complete replacement for planning, reserves or reliable protection.

The balancing act is institutional as well as electrical. The authors identify interoperability, coordination among multiple inverter-based resources, a lack of harmonized grid-code requirements, and protection coordination as unresolved issues. A grid code must say what behavior equipment should deliver during normal operation and disturbances. If each vendor’s controls are developed and validated in isolation, the system operator may discover interactions only after devices are connected—or after an oscillation appears in the field.

Figure 6: Example of dual-infeed HVDC system with LCC and VSC links in an islanded grid. Figure from [18].
Figure 6: Example of dual-infeed HVDC system with LCC and VSC links in an islanded grid. Figure from [18]. Source: Anup Joshi, Luis A. Garcia-Reyes

The Hawaiian example underlines the point: a controller intended to help form the grid can itself become part of an oscillation. The Faroe Islands example underlines the complementary one: with suitable equipment and tuning, a battery can help a system operate at 100% wind. Neither case is a simple verdict for or against GFM. Together, they show that the value lies in system design and verified performance, not in a label on a converter.

What’s Next

The next step is to move from broad promise to clear, testable requirements. The report calls for harmonized grid codes that specify GFM functionality, planning methods tailored to island conditions, better interoperability, and coordination among converter controls and protection devices. Engineers will need to validate models against field behavior and test how controls perform under both ordinary variations and severe events. Protection schemes, including UFLS, should be assessed alongside fast battery response rather than tuned as if the grid still behaved like one dominated by rotating generators.

There are also questions of scale and energy. A converter can respond rapidly, but its ability to sustain support depends on the energy source and operating limits behind it. The Faroe battery’s power rating and stored energy describe different capabilities: how quickly it can deliver power, and for how long. The report’s example is persuasive evidence of what a carefully designed installation can do, but it does not establish the storage, reserve or control needs for every island system.

The case study points toward another research need: quantified comparisons across grid strengths, control settings and operating conditions. The executive summary says the GFM converter improves small-signal stability in the examined weak grid, but broader adoption will require evidence that remains robust when many devices interact, power flows change and faults occur. Small-signal stability is only one piece; severe disturbances, voltage recovery, protection behavior and restoration must all be examined.

Island grids make a global transition visible in miniature. They show how quickly low inertia and weak connections can turn renewable variability into a reliability challenge—and how power electronics might help, if they are designed as part of the grid rather than as isolated products. The opportunity is real: cleaner electricity with less dependence on shipped fuel, and systems better able to ride through disturbances. The path runs through both engineering and governance: converters that can form a grid, and institutions capable of making them work together.