A thermostat can save one floor money—and quietly bill the floor above
A simulated two-story house seemed to save $103 over a winter when an advanced controller managed only its first floor. But the upstairs heating bill rose by $40, leaving the whole house with just $62 in savings. The first-floor report overstated the actual benefit by 65%.
That gap is not a bookkeeping curiosity. It exposes a blind spot in how building upgrades are often evaluated: a controller can make the zone it manages look more efficient by drawing heat from a zone it does not. If the second zone’s heating system pays for that transferred warmth, a report that measures only the first floor misses part of the cost. The result can turn a real but modest improvement into a much more impressive claim.
Khabbazi and Kircher test how to identify and correct that bias. Their 90-day simulation suggests a useful practical distinction: a simple ratio of heat-transfer pathways can serve as a conservative warning before a field demonstration, while a fuller calculation can recover the whole-building savings from temperature records, prices, and estimates of building properties. But the simple ratio becomes loose when a controller makes savings by shifting heating to cheaper hours rather than simply running a room colder.
The Science
Buildings exchange heat across boundaries. A room loses heat through exterior walls and windows, but it can also gain or lose heat through partitions, floors, and ceilings connected to neighboring spaces. A thermal zone is a modeled region treated as sharing one temperature; in a real building, it might correspond to a room or a whole floor. The rate of heat transfer depends on the temperature difference and the conductance of the connection, a measure of how readily heat passes through it.
The problem arises when an advanced heating, ventilation, and air-conditioning controller operates only some zones. Imagine that it lets one room run cooler than its usual setpoint. Heat then flows from warmer neighboring zones into that room. The neighbors’ heating equipment must replace the transferred heat, but if evaluators count only the controlled room, they record its lower heating cost and omit the extra cost next door. In measurement and verification—the process of establishing whether an energy measure actually saved energy—this is an interactive effect: a consequence outside the chosen measurement boundary.
The authors build on an earlier theorem that describes this effect for a network of thermal zones. In the two-zone example here, the first floor is under advanced control, while the second floor remains at its ordinary setpoint. The building loses heat outdoors from both floors, and heat also moves between them. The theorem says the zone-only overstatement depends on the heat-transfer link between floors, how much colder the controlled zone becomes, and the price of heat supplied by the uncontrolled zone (Khabbazi and Kircher, 2026).
A second piece of the theorem separates two ways a controller can save. It can reduce heat loss by keeping a zone colder; or it can shift heating in time, warming the building when energy is cheap and letting it coast when energy is expensive. The latter uses the building’s thermal mass—the heat stored in air, furnishings, and structure—as a temporary battery. The researchers summarize the relative importance of shifting versus running colder with a ratio, which helps explain why the same building can produce different accounting errors under different electricity tariffs.
To test the theory, the authors simulated a representative two-story detached house in West Lafayette, Indiana, through December, January, and February. They used hourly weather and solar data, assigned one thermal zone to each floor, and had a receding-horizon model predictive controller manage the first floor. Model predictive control (MPC) repeatedly plans ahead over a fixed future window, acts on the next step, then plans again as conditions change. The second floor stayed at its setpoint.
The simulation crossed two heating systems—a heat pump and electric resistance heat—with two electricity prices: a flat tariff and a time-of-use tariff, which charges different rates at different hours. The MPC had a 24-hour planning horizon and, importantly, perfect knowledge of the coming weather, prices, and internal heat gains. This is a controlled test of the accounting theory, not a field trial measuring how a real controller performs amid imperfect forecasts and messy building operations.
Figure 1 shows the house as a thermal network: two floors connected to each other and to the outdoors. The exterior envelope is better insulated than the assembly between floors, so the inter-floor connection is relatively strong. That matters because heat can more readily cross between the zones than escape through the exterior.
What They Found
The first result is simple and consequential: counting only the controlled floor overstated whole-house savings in all four simulated cases. Under the heat-pump/time-of-use combination, first-floor costs fell from $350 to $247, a perceived saving of $103. The second floor’s cost rose from $731 to $771 as it supplied some of the heat flowing downstairs. Whole-house savings were therefore $62, not $103.
Under other combinations, the same accounting mismatch appeared, though the dollar amounts varied with the heating plant and tariff. The resistance-heating cases had larger dollar totals because each unit of delivered heat cost more. Those absolute totals are less useful for comparing the underlying bias than the relative errors.
Seasonal apparent savings versus whole-house savings
The zone-only perceived savings include the cost increase imposed on the second floor; whole-house savings account for both floors.
| Label | Value |
|---|---|
| HP-TOU perceived | 103 USD |
| HP-TOU whole house | 62 USD |
| HP-Flat perceived | 40 USD |
| HP-Flat whole house | 21 USD |
| Res-TOU perceived | 271 USD |
| Res-TOU whole house | 163 USD |
| Res-Flat perceived | 136 USD |
| Res-Flat whole house | 71 USD |
The paper tests a pre-demonstration screening number: the conductance between the controlled and uncontrolled zones divided by the controlled zone’s conductance to outdoors. In this house, that ratio is 1.905. Under conditions where the thermal price changes slowly, the ratio is predicted to equal the relative overstatement. In the simulations it acted as an upper bound in all four cases—but its closeness to the measured error depended on the tariff.
With resistance heat and a flat tariff, the measured relative error was exactly 1.905, matching the conductance ratio. With a heat pump and a flat tariff it was 1.855, within about 3% of the ratio. A heat pump’s efficiency changes with outdoor temperature, so even a nominally flat electricity rate does not create a perfectly constant price for delivered heat. Still, the simple ratio worked closely in that case.
Under time-of-use pricing, the measured errors were much smaller: 0.72 for resistance heat and 0.65 for the heat pump. Those values are roughly a third of the 1.905 screening ratio. The controller was not relying mainly on keeping the first floor cold. It was preheating ahead of expensive hours and coasting through them, shifting a substantial part of its savings through time.
Measured relative overestimation across four cases
The paper reports the ratio of zone-only accounting error to true whole-house savings. The slow-price conductance-ratio limit is 1.905 in every case.
| Label | Value |
|---|---|
| HP-TOU | 0.65 |
| HP-Flat | 1.855 |
| Res-TOU | 0.72 |
| Res-Flat | 1.905 |
That difference is visible in the savings breakdown. Under the time-of-use tariff, load shifting contributed $41 of the heat pump’s $62 in true savings, and $101 of the resistance system’s $163. Under flat pricing, the contribution was only $0.77 for the heat pump and zero for resistance heat. The flat-rate controller mostly saved by lowering the first-floor temperature; the time-of-use controller also used the building as a store of heat.
Time-of-use load shifting contributes to true savings
Under time-of-use prices, the controller’s savings include a substantial contribution from storing heat at cheaper times and coasting during expensive periods.
| Label | Value |
|---|---|
| HP-TOU load shifting | 41 USD |
| Res-TOU load shifting | 101 USD |
| HP-Flat load shifting | 0.77 USD |
| Res-Flat load shifting | 0 USD |
The authors’ full correction accounts for both mechanisms. It uses the controlled zone’s temperature history, the time-varying price of heat, and estimates of thermal conductances and heat capacity. In each of the four simulated cases, the correction recovered the true whole-house savings, and the theorem’s predicted relative error matched the measured relative error. It did not require an energy baseline for the controlled zone.
That exact agreement should be interpreted in context. The simulation and correction share the same underlying thermal model, so the result demonstrates consistency within the model, not independent validation against a real building. The paper’s most useful practical finding is therefore not that the correction has been proven under every field condition, but that it can be calculated and that the simpler screening ratio’s failure mode can be understood.
Figure 3 shows the controller’s behavior during the four coldest days. Under time-of-use pricing, the first floor warms before expensive periods and then coasts; under flat pricing, it spends more time near the bottom of the permitted comfort range. In both patterns, the second floor’s heating system works harder whenever the first floor is cooler than its baseline.
Why This Changes Things
Building-control demonstrations are often conducted in a subset of a larger building. That can be sensible: a research team may have access to a few rooms, or a retrofit may affect only one wing. But the boundary used to report savings must still include the costs the intervention pushes elsewhere. Otherwise, a controller that transfers heating demand across a partition can appear more effective than it is for the building as a whole.
The conductance ratio gives evaluators an early warning. It requires estimates of how strongly the controlled zone connects to its neighbor and to outdoors—not a season of energy data. A high ratio signals that neighboring zones may bear a substantial share of the heating load when the controlled zone cools. That is valuable before a field trial, when measurement boundaries and sensor plans can still be changed.
The study also gives the simple rule a limit. It works best when price changes little and savings come from reducing heat loss. Where a tariff has large time-based swings, thermal mass lets the controller shift demand, and the ratio can overstate the error substantially. The tariff may matter more than the choice between a heat pump and resistance heating: the two plants’ relative errors were similar within each tariff type, while switching tariff types changed them by about a factor of three.
For building owners, utilities, and policymakers, measurement quality affects more than a paper’s conclusion. Reliable savings claims help determine whether a technology merits investment, whether a utility program should scale, and whether efficiency improvements are reducing energy use rather than relocating it. If demonstrations systematically measure only the controlled zones, their results can mislead both skeptics and supporters: inflated claims invite disappointment, while poorly measured benefits make genuinely useful control strategies harder to distinguish.
The findings also underline that “energy savings” and “cost savings” are not interchangeable. Time-of-use control may reduce bills by moving consumption away from expensive periods without reducing heat demand by the same amount. The paper’s accounting framework is designed for linear costs of heating load, including energy cost under its assumptions; it does not directly settle questions about peak demand charges or other nonlinear incentives.
What’s Next
The authors are explicit about the model’s boundaries. Heat transfer is treated as linear, and cost is linear in heating load. Real heat pumps may switch to backup resistance heat in cold weather, and their efficiency can depend on part-load operation; either can make cost nonlinear. The house also has no infiltration, assumes an adiabatic slab, and uses a single season of weather. The controller knows future weather, prices, and gains perfectly, an advantage that real systems do not have.
The two floors are each represented by one thermal node. That is a useful simplification, but actual buildings contain slower layers of structure that store heat over longer periods. The authors note that adding these deeper thermal masses could increase the importance of load shifting under time-of-use pricing, potentially widening the gap between the conductance ratio and the observed error. Air movement between floors is also not modeled explicitly, though it could be approximated as another pathway for heat transfer.
The theorem itself applies to more complicated networks with many zones, but this paper tests a deliberately small two-zone case. Field work will need to examine how well the required conductance and heat-capacity estimates can be obtained, how uncertainty in those estimates propagates into corrected savings, and whether the correction remains robust when the building departs from the model. Those are practical questions, not reasons to ignore the problem.
The broad lesson is that a building is a connected system, even when a demonstration controls only one room. Before celebrating a local efficiency gain, ask who supplied the heat that room stopped using. With appropriate boundaries—or a correction that accounts for the thermal connections—advanced control can be judged on what it saves for the building, rather than on what it shifts to the next floor.