A wiring rearrangement cut charger balancing stress—and raised efficiency 5.6%

A wiring rearrangement cut charger balancing stress—and raised efficiency 5.6%
Six Modules Prototype size
Stable Operation Demonstrated Fault testing
5.6% efficiency increase
63% voltage difference reduction
14.5% peak balancing current reduction

A 63% reduction in the largest voltage difference between converter modules came from changing their grouping—not from adding another conversion stage. In a laboratory solid-state transformer, that rearrangement also cut peak balancing current by 14.5% and raised measured efficiency by about 5.6% at rated power. The result addresses a quiet but consequential design problem for high-power chargers: when one output is busy and another is idle, how far must electricity travel inside the equipment to get where it is needed?

Electric-vehicle fast-charging stations often need several isolated outputs, each serving a vehicle whose demand changes independently. A conventional architecture can create a shared DC bus and then place a separate converter at each outlet. Those converters regulate each port and provide electrical isolation where required, but they add components and another high-power conversion step. The architecture studied here aims to deliver multiple isolated outputs directly from the transformer’s own converter modules. Its promise is fewer stages; its challenge is sharing power when the ports are unevenly loaded.

The Science

A solid-state transformer, or SST, converts power between a medium-voltage grid and lower-voltage systems using semiconductor converters and high-frequency electrical isolation. Unlike a conventional transformer, it can also control power flow and potentially support functions such as reactive-power management. The paper focuses on a cascaded H-bridge (CHB) SST: a series of power-conversion submodules that together handle the grid-side voltage.

Each submodule has an isolated DC/DC stage, which can supply a low-voltage DC output. One module usually cannot provide all the power needed by a practical charging port, so several modules’ outputs are connected in parallel to form one port. In this single-isolation-stage design, the port is supplied directly by those outputs rather than by an additional downstream high-power converter. The term “single isolation stage” describes the power-conversion architecture; it does not mean that the equipment has only one converter component.

The problem appears when output demands diverge. Imagine one charging outlet drawing heavily while others draw little or nothing. The transformer’s grid-side modules still need to operate as part of the overall system, but the DC/DC stages associated with unloaded ports cannot deliver their available power to those ports. Inter-submodule balancing circuits create paths to transfer that power toward the loaded port. They act as internal bridges, allowing modules to share energy and helping keep their DC-link voltages—the voltages across their internal capacitors—from drifting too far apart.

The geometry of those bridges matters. In the straightforward “sequential” arrangement, adjacent modules are assigned in blocks to the same output. If the first port’s modules occupy one part of the chain and the other ports’ modules sit farther along it, power from a distant idle group may have to pass through several balancing circuits before reaching the loaded group. Circuits nearer the destination can end up carrying the accumulated contribution from more distant modules. That increases current stress and the amount of power processed through the balancing network, which can add losses.

The authors’ proposed optimal power-flow (OPF) grouping interleaves modules assigned to different ports. Instead of placing all modules for one output together, it distributes that output’s modules along the cascade. Under unequal loading, modules that need to send power and modules that need to receive it are therefore more likely to be neighbors. Figure 4 shows the proposed assignment; the contrast with sequential grouping is visible in Figure 2.

Fig. 4: Proposed OPF grouping topology for single-isolation-stage SST
Fig. 4: Proposed OPF grouping topology for single-isolation-stage SST Source: Yi Hao, Krzysztof Puczko
Fig. 2: Straightforward sequential grouping topology for single-isolation-stage SST
Fig. 2: Straightforward sequential grouping topology for single-isolation-stage SST Source: Yi Hao, Krzysztof Puczko

The idea is a wiring and grouping strategy, not a claim that balancing becomes unnecessary. The circuits still transfer power, and their control still has to maintain stable voltages. The design target is to make redistribution more local, reducing long transfer paths and avoiding the concentration of power in a few links.

What They Found

The analytical comparison starts with a worst-case loading pattern: one end output is fully loaded and the others are unloaded. The paper derives expressions for the total balancing power handled by the circuits. For fixed number of ports, the sequential grouping expression grows with the square of the number of submodules. The proposed arrangement’s expression grows linearly with that number, under the assumptions of the model. This distinction matters as systems scale: an arrangement whose balancing burden rises faster can demand increasingly stressed hardware as more modules are added.

For example, applying the paper’s equations to a two-port case gives a normalized balancing-power requirement of 1, 4, and 9 single-module input-power units for sequential grouping at 2, 4, and 6 modules, respectively. The corresponding interleaved values are 1, 2, and 3. These are calculations from the analytical expressions, not measured powers from the prototype. The general lesson is less about those particular illustrative counts than about scaling: the arrangement can prevent distant contributions from accumulating along one transfer route.

Analytical balancing-power requirement, illustrative module counts

Values derived from the paper’s analytical expressions, normalized by single-submodule input power Psm. For m=2, sequential P/Psm=n²/4 and OPF P/Psm=n/2.

Analytical balancing-power requirement, illustrative module counts
LabelValue
n=2 sequential1
n=2 interleaved1
n=4 sequential4
n=4 interleaved2
n=6 sequential9
n=6 interleaved3

The team tested the proposal on a six-submodule laboratory prototype. Under the same highly unbalanced operating conditions, the proposed grouping reduced the maximum submodule DC-link voltage difference by 63% and the peak balancing current by 14.5%. At rated power, measured efficiency improved by approximately 5.6%. Those are experimentally reported comparisons, rather than projections from the analytical model. The paper’s central result is that a topology-level change translated into observable changes in voltage balance, current stress, and system efficiency.

Measured gains with interleaved grouping

Reported comparison under the same highly unbalanced operating conditions; efficiency result is at rated power.

Measured gains with interleaved grouping
LabelValue
Maximum DC-link voltage difference reduction63 %
Peak balancing current reduction14.5 %
Measured efficiency improvement at rated power5.6 %

The distinction between the two current and voltage findings is useful. Lower peak balancing current suggests less electrical stress on the most heavily loaded balancing path. A smaller maximum DC-link voltage difference indicates that the modules’ internal energy-storage voltages stayed closer together. The study does not establish that these changes guarantee a particular lifetime improvement; that would require additional reliability and long-duration testing. But both measurements address practical burdens that designers must manage.

The work also examines what happens when a submodule is bypassed after a fault. In modular converters, bypassing a failed unit can permit continued operation at reduced capability. Here, the balancing links add another complication: the remaining modules must still be able to redistribute power after the system’s network of modules changes. The authors develop a coordinated bypass strategy, evaluate remaining output-power capability for faults in different conversion stages, and report experimentally demonstrated stable post-fault operation. The material supplied for this digest does not include numerical post-fault capacity results, so no specific retained-power figure can be stated.

The proposed power routes are illustrated for a three-port, nine-module example. With only Port 1 loaded, sequential grouping leaves remote idle groups separated from the active group by intermediate modules. In the interleaved arrangement, active and inactive port assignments recur along the chain, bringing potential sources and destinations closer. Figure 5 makes that localized redistribution visible.

Fig. 5: Illustration of power flow paths in the proposed OPF grouping topology n=9 and m=3 (Port1 loaded only)
Fig. 5: Illustration of power flow paths in the proposed OPF grouping topology n=9 and m=3 (Port1 loaded only) Source: Yi Hao, Krzysztof Puczko

Why This Changes Things

The appeal is straightforward: remove a high-power converter stage without giving up independently regulated, isolated outputs. That could matter in fast-charging stations, where vehicles connect and draw power on separate schedules. It may also matter in some data-center designs that distribute power through isolated, independently regulated outputs. The paper is careful that data centers often use a shared DC bus and may not require isolated conversion at every rack; this architecture is an alternative for particular distribution choices, not a universal replacement.

The study’s broader engineering point is that component count is only one measure of simplicity. Removing an output converter can reduce hardware, but power still has to flow from where it is produced to where it is consumed. If the internal balancing network must process large amounts of power across long paths, some efficiency gains may be lost to current stress and conversion losses. The grouping topology changes the route itself, making the architecture’s power-sharing mechanism more compatible with independently varying loads.

This is a useful example of system design producing benefits without a novel material or a more powerful semiconductor. The authors did not make the output demands more predictable. They changed the arrangement so the hardware can respond to their unpredictability with shorter internal transfers. In a charging station, that could support a more modular relationship between outlets and the grid-side conversion equipment; any real-world cost or footprint advantage would still need to be demonstrated in a full system.

The evidence also has limits. A six-submodule prototype validates an important principle, but it is not a commercial fast-charging site or a data center operating across a broad range of temperatures, faults, and load profiles. The headline efficiency change applies to the reported experimental conditions at rated power. The supplied text does not give enough detail to assess every operating point, compare lifetime costs, or estimate system-wide energy savings. Nor should a relative efficiency improvement be confused with a 5.6-percentage-point increase in absolute efficiency; the abstract reports an improvement of approximately 5.6%, without specifying that interpretation as percentage points.

Likewise, “optimal” should be read in the context of the paper’s power-flow objective. The grouping aims to reduce balancing-power paths and processed power under the analyzed assumptions. Real systems must also accommodate insulation, packaging, thermal design, protection coordination, manufacturability, and control constraints. Those may shape the final physical layout even when the power-flow arrangement is attractive.

What’s Next

The next test is scale and variety. Researchers and engineers can examine how the grouping performs with more submodules and output ports, with changing loads rather than a single severe imbalance, and across the full operating range of the converters. The paper’s model offers a way to compare candidate arrangements, while measurements in larger prototypes could reveal whether the predicted reduction in balancing burden persists once parasitic effects, control limits, and thermal constraints enter the picture.

Fault operation deserves similar scrutiny. Demonstrating stable post-fault operation is an important step, but deployment decisions depend on how much output remains available for each kind of failure, how quickly the system detects and bypasses a fault, and whether neighboring balancing circuits can tolerate the altered power routes. Quantified endurance tests and clear fault-specific capacity maps would help operators judge resilience.

If those questions hold up, the contribution could be practical precisely because it is modest: a better assignment of modules, rather than another major power stage. As charging networks add ports and their demands become less synchronized, the route taken by power inside a transformer can matter as much as the amount of power it converts. This prototype suggests that topology can make a leaner architecture more capable of coping with uneven demand—and gives designers a testable route toward multi-output systems that waste less effort moving power around inside themselves.